아날로그 액세서리


 
FMR-1000-RA 제어 장치 미포함 LCD 신호 표시기 FPA-1000
  • LED status indicators
  • 80‑character LCD display
  • Piezo sounder
  • Navigation buttons
  • Acknowledge key
 
 
FMR-1000-RCMD 제어 장치 포함 LCD 신호 표시기 FPA-1000
  • LED status indicators
  • 80‑character LCD display
  • Piezo sounder
  • Navigation buttons
  • Operations keys for drill, reset, silence, and acknowledge
 
 
FLM-325-I4-A Contact Monitors
  • Monitors Normally Open (NO) or Normally Closed (NC) contacts
  • Monitored Normally Closed (NC) contacts can be configured with or without EOL resistor
  • Module address programming with the D5070 Analog Device Programmer
  • Bi‑colored LED provides module status
  • Digital data communications and power over a two‑wire circuit
  • EEPROM addressing
 
 
FLM-325-2R4-A Dual Relay Modules
  • Two independently configurable Form C contacts
  • Contacts are rated 1 A at 30 VDC or 0.5 A at 125 VAC
  • Module address programming with the D5070 Analog Device Programmer
  • Bi‑colored LED provides module status
  • Digital data communications and power over a two‑wire circuit
 
 
FLM-325-NA4 Supervised Output Modules
  • Contacts are rated 2 A at 24 VDC
  • Flexible application and quick response to emergency conditions
  • Can be alarmed or reset by zone or by individual address
  • Module address programming with the D5070 Analog Device Programmer
  • Bi‑colored LED provides module status
  • Digital data communications and power over a four‑wire circuit
 
 
FLM‑325‑N4 Supervised Output Module
  • Programmable evacuation tones of 4 s with a granularity of 250 ms
  • Contacts are rated 2 A at 30 VDC
  • Flexible application and quick response to emergency conditions
  • Can be alarmed or reset by zone or by individual address
  • Module address programming with the D5070 Analog Device Programmer between 1‑127
  • Bi‑colored LED provides module status
  • Digital data communications and power over a four‑wire circuit
 
 
FLM-325-CZM4 FPA-1000용 컨벤셔널 구역 모듈
  • Provides a zone of up to 25 conventional smoke detectors (depending on detector type)
  • Supervises auxiliary power supply for conventional detectors
  • Compatible with Class B (Style B) or Class A (Style D)
  • Module address programming with the D5070 Analog Device Programmer between 1 and 127
  • Bi‑colored LED provides module status
  • Digital data communications and power over a four‑wire circuit
 
 
D7035 Octal Relay Modules
  • Eight Form C programmable relay outputs
  • D7035 mounts conveniently inside the FACP enclosure; no separate enclosure needed
  • D7035B includes mounting skirt and enclosure for mounting outside of the FACP enclosure
  • Up to two modules are supported by the FACP
 
 
FLM-325-ISO FPA-1000용 단락 차단기
  • Automatic verification of data line for short circuit
  • Contacts are rated to 1 A at 30 VDC
  • Can be placed at any location on SLC loop
  • 256 devices at maximum per loop for Class A (Style 7)
  • Yellow LED provides data line status
 
 
FPE-1000-SLC FPA-1000용 플러그인 SLC 모듈
  • Signaling Line Circuit (SLC) is power-limited and supervised
  • Configurable as one Class A Style 6 or 7 or two Class B Style 4 circuits
  • Up to 254 detectors and modules, or 127 analog sounder bases in combination with suitable detectors
 
 
FPE-1000-NE 네트워크 카드, 3개 이더넷
  • Provides three Ethernet ports using CAT 5 or better cable
  • Uses simple plug-in connection to the FPA‑1000‑V2
  • Connects as either Class A or Class B
  • Uses standard RJ45 connections
  • Provides second power input port for normal network operation during maintenance
 
 
FPE-1000-NF 네트워크 카드, 1개 이더넷, 2개 광섬유
  • Provides media type change through RJ45 and fiber optic connections
  • Provides one Ethernet port using CAT 5 or better cable
  • Uses simple plug-in connection to the FPA‑1000‑V2
  • Connects as either Class A or Class B
  • Provides second power input port for normal network operation during maintenance
 
 
FPE-1000-NW 네트워크 카드, 1개 이더넷, 2개 유선
  • Provides media type change through RJ45 and wired connections
  • Provides one Ethernet port using CAT 5 or better cable
  • Uses simple plug-in connection to the FPA‑1000‑V2
  • Connects as either Class A or Class B
  • Provides second power input port for normal network operation during maintenance
 
 
FLM-325-IM 후면 장착함 내 장착용 접점 모니터
  • Digital data communications and power provided over a two-wire circuit
  • Class B circuit for dry contact devices
  • Module address programming (1-254) with the D5070 Analog Device Programmer
 
 
FLM-325-2I4 FPA-1000용 이중 입력 모듈
  • Two independent contact monitoring circuits
  • Monitors Normally Open (NO) or Normally Closed (NC) contacts
  • Monitored Normally Open (NO) contacts can be configured with or without EOL resistor
  • Module address programming with the D5070 Analog Device Programmer between 1‑127
  • Bicolored LED provides module status
  • Digital data communications and power over a two‑wire circuit